GT30: Can I switch screens by using both the function switch and programmable controller?
- ID:
- 204
- Issued:
- Dec 28th, 2009
- Updated:
- May 16th, 2013
GT30: Can I switch screens by using both the function switch and programmable controller?
- ANSWER
- You can switch the screens using the function switch by directly designating a screen number regardless of the controller status. You can also switch the screens from the controller by writing the screen number data in DT0. However, if you use both methods, there will be a difference between the screen switching data in DT0 and the currently displayed screen data in DT2, and screen switching by the controller may be impossible. In such cases, set the screen switching data in DT0, and then set and reset the forced screen switching flag (internal relay RE).