A photocoupler is used in the home position input circuit of FP2 positioning unit and there is also one with a driver output in the Z phase signal output of the servo driver.
- ID:
- 811
- Issued:
- Dec 25th, 2009
- Updated:
- May 17th, 2013
A photocoupler is used in the home position input circuit of FP2 positioning unit and there is also one with a driver output in the Z phase signal output of the servo driver.
Can direct connection be made here?
- ANSWER
Two impedances, 220 Ω (560Ω) and 1.6 KΩ (3.0 KΩ), are available for the home position input of the FP2 positioning unit and each has its own terminal. When connecting a line driver, please connect it to the 220 Ω (560Ω) terminal.
Note: The impedance value in brackets is for the multi-function type.